Inspection Checklist - Hazard

Performing
a Fire Inspection Checklist
For
Occupancy Type H - Hazard
| Sub task |
Inspection step |
Code compliance |
Comments/ Location |
|
| Examine Housekeeping Issues |
Yes |
No |
||
|
|
Verify that: |
|
|
|
| 315.2 |
1. Storage of combustible materials is orderly. |
|
|
|
| 315.2 |
2. Storage is separated from heaters or heating devices by distance or shielding. |
|
|
|
| 315.2.1 |
3. Storage is at least 18” below sprinkler head deflectors or 2 ft. below ceiling in non-sprinklered areas. |
|
|
|
| 315.2.2 |
4. Exits and exit enclosures are kept free from combustible materials. |
|
|
|
| 315.2.3 |
5. Boiler, mechanical, and electrical equipment rooms are kept free from and combustible materials. |
|
|
|
| 315.2.4 |
6. Any attic, under-floor, and concealed spaces used for storage of combustible materials is protected on the storage side as required. |
|
|
|
| 315.3 |
7. Outside storage of combustible materials is not located within 10 ft. of property line unless exception allows. |
|
|
|
| 304.3.2 |
8. Combustible waste containers larger than 40 gallons have lids and are constructed of metal or approved combustible material. |
|
|
|
| 304.3.3 |
9. Dumpsters and containers more than 40.5 cubic ft. stored outside and not within 5 ft. of combustible walls, openings or under eave lines. |
|
|
|
| 304.3.1 |
10. Oily rags or other materials subject to spontaneous ignition are stored in a listed disposal container and removed daily as required. |
|
|
|
| Examine Miscellaneous Areas |
Yes |
No |
Comments / Location |
|
|
|
Verify that… |
|
|
|
| 505.1 |
1. Approved address numbers are plainly legible and visible from the street fronting the property. |
|
|
|
| 506.1 |
2. Key box is properly installed, if required. |
|
|
|
| 503.4 |
3. Fire apparatus roads are unobstructed. |
|
|
|
| 503.2.1 |
4. Fire apparatus roads are not less than 20 ft, with a minimum height unobstructed of 13 ft. 6 in. |
|
|
|
| 404.2 |
5. An approved fire safety and evacuation plan has been prepared and is maintained. |
|
|
|
| 405.2 |
6. Emergency evacuation drills have been conducted quarterly by all employees and the emergency response team as required, and records have been maintained. |
|
|
|
| Examine Fire Protection System |
Yes |
No |
Comments / Location |
|
|
|
Verify that… |
|
|
|
| Tbl 906.3(1) 906.1 |
1. One 2A fire extinguisher is installed in low hazard office areas per 6000 sq. ft. |
|
|
|
| Tbl 906.3(1) 906.1 |
2. One 2A fire extinguisher is installed in moderate hazard areas per 3000 sq. ft. |
|
|
|
| Tbl 906.3(1) |
3. The maximum travel distance to an extinguisher is 75 feet. |
|
|
|
| 906.5 |
4. Extinguishers are located in conspicuous locations where they will be readily accessible and immediately available for use. |
|
|
|
| 906.6 |
5. Extinguishers are not obstructed or obscured from view. |
|
|
|
| 906.7 |
6. Handheld extinguishers are not housed in cabinets or installed on hangers or brackets. |
|
|
|
| 906.9 |
7. Fire extinguishers are installed so that its top is no more than 5 ft. above the floor if less than 40 lbs. and if over 40 lbs no more than 3.5 ft. above the floor. |
|
|
|
| Tbl. 906.1 |
8. Additional required extinguishers are in place. |
|
|
|
| 906.2 |
9. All fire extinguishers have current service tag indicating service was conducted. |
|
|
|
| 903.4 |
10. All valves on the sprinkler are electronically supervised if system has more than 20 heads. |
|
|
|
| 901.6 NFPA 13, 6.2.6.2.2 |
11. All sprinkler heads or cover plates are clear of paint unless part of factory installed paint when head was produced. |
|
|
|
| 901.6 |
12. All fire detection, alarm, and extinguishing systems are being maintained in an operative condition. |
|
|
|
| 901.6.2 |
13. Records are available for all system inspections, tests and maintenance for last 3 years and available if requested. |
|
|
|
| 508.5.5 |
14. A 3 ft. clearance has been maintained around all fire hydrants unless otherwise approved. |
|
|
|
| 907.20.5 |
15. Fire alarm systems have been maintained in an operative condition. |
|
|
|
| 903.2.4.1 |
16. An automatic fire sprinkler system is present. |
|
|
|
| 908.2 |
17. Emergency alarms are present in an HPM facility. |
|
|
|
| 908.2 |
18. A continuous gas detection system is present for HPM glasses where required. |
|
|
|
| Examine Electrical System |
Yes |
No |
Comments / Location |
|
|
|
Verify that… |
|
|
|
| 605.4.1 |
1. Re-locatable power taps are of the polarized or grounded type and are equipped with overcurrent protection and listed. |
|
|
|
| 605.4.2 |
2. Re-locatable power taps are directly connected to a permanently installed receptacle. |
|
|
|
| 605.4.3 |
3. Re-locatable power taps do not extend through walls, ceilings, floors, under doors or floor coverings or are subject to damage. |
|
|
|
| 605.5 |
4. Extension cords do not serve as a substitute for permanent wiring. |
|
|
|
| 605.5 |
5. Extension and flexible cords are not affixed to the structure, extended through walls, ceilings or floors. |
|
|
|
| 605.5.1 |
6. Extension cords are plugged directly into an approved receptacle, power tap, or multi-plug adapter |
|
|
|
| 605.5.1 |
7. Any extension cord only serves one portable appliance unless an approved multiplug extension cord is used. |
|
|
|
| 605.5.3 |
8. Extension cords do not contain splices or damage. |
|
|
|
| 605.5.4 |
9. Extension cords are grounded if serving grounded portable appliances. |
|
|
|
| 605.5.2 |
10. Extension cord ampacity is greater than the rated ampacity of the portable appliance served by the cord. |
|
|
|
| 605.3 |
11. Proper working spaces are being maintained in and around service equipment. |
|
|
|
| 605.6 |
12. All electrical boxes and wiring is properly covered. |
|
|
|
| 605.8 |
13. Electrical motors are maintained free from excessive accumulations of oil, dirt, waste and debris. |
|
|
|
| 605.9 |
14. Temporary wiring is only being used for less than 90 days unless for construction, remodeling, repair or demolition of building. |
|
|
|
| 605.9.1 |
15. Temporary wiring is properly attached. |
|
|
|
| 605.4 |
16. No multiplug adapters, such as cube adapters, unfused plug strips, or any other device prohibited by the Electrical Code are present. |
|
|
|
| 605.3.1 |
17. Doors into electrical control panel rooms are properly marked with a sign. |
|
|
|
| 1803.7.2 |
18. Electrical equipment and devices within 5 ft. of workstations in Group H5 are properly installed. |
|
|
|
| Examine Exits |
Yes |
No |
Comments / Location |
|
|
|
Verify that… |
|
|
|
| Tbl. 1019.1 Tbl. 1019.2 Tbl. 1015.1 |
1. The minimum required exits are present for the occupant load. |
|
|
|
| 1008.1.8 |
2. Egress doors are readily openable from the egress side without the use of a key or special knowledge or effort. |
|
|
|
| 1008.1.9 |
3. Latches are not present unless it is panic hardware or fire exit hardware. |
|
|
|
| 1011.3 |
4. Exit signs are internally or externally illuminated or of approved self-luminous type. |
|
|
|
| 1011.5.3 |
5. Exit signs are visible under emergency illumination conditions. |
|
|
|
| 1011.1 |
6. Exits and exit access doors are marked by an approved exit sign visible from any direction of egress travel where required. |
|
|
|
| 1011.1 |
7. Required exit signs are no further than 100 feet from any point in the corridor. |
|
|
|
| 1011.5.3 1027.5 |
8. Exit signs are properly illuminated for a duration of not less than 90 minutes by testing on proper back-up supply. |
|
|
|
| 1003.6 |
9. Means of egress do not have any obstructions in the required width areas. |
|
|
|
| 1003.6 |
10. Means of egress are not reduced in width along the path of egress travel |
|
|
|
| 1008.1.1 1027.7 |
11. Exit doorways are not less than 32” in width or 28” in existing buildings. |
|
|
|
| 1025.9.1 |
12. Aisles of are proper width. |
|
|
|
| 1021.2 |
13. Exit passageways are of sufficient width for occupant load. |
|
|
|
| 1008.1.2 |
14. Installed panic hardware is rated to unlatch with a maximum of 15 lbs force applied to the bar and can be set in motion with 30 lbs of force. |
|
|
|
| 1008.1.8.4 |
15. Manually operated flush bolts or surface bolts are not installed on exit doors |
|
|
|
| 1006.3 |
16. Exit access corridors, passageways, exit stairways, rooms, exit discharge areas, with 2 or more required exits are illuminated in case of a power failure. |
|
|
|
| 1008.1.3.4 |
17. Access controlled entrance egress doors properly identified, installed correctly and have a manual unlocking device. |
|
|
|
| Tbl 1016.1 |
18. Travel distances to exits are present as required. |
|
|
|
| 1008.1.9 |
19. Panic or fire exit hardware is installed as required. |
|
|
|
| Examine Hazardous Materials Area |
Yes |
No |
Comments / Location |
|
|
|
Verify that… |
|
|
|
| 105.6.16 |
1. Class I liquids in excess of 5 gallons inside or 10 gallons outside are properly permitted. |
|
|
|
| 2703.9.8 |
2. Storage of incompatible materials is separated properly if in containers over 5 lbs. or .5 gallon. |
|
|
|
| 3404.3.3.5.3 |
3. Shelf storage of flammable and combustible liquids is orderly. |
|
|
|
| 3404.3.5.1 |
4. Class I flammable liquids are not located in the basement. |
|
|
|
| 2703.5 |
5. Hazardous material is identified with a placard. |
|
|
|
| 3404.2.2 |
6. Tank cars and vehicles are not being used as storage tanks of flammable and combustible materials. |
|
|
|
| 3404.2.3.2 |
7. No Smoking signs are posted as required in storage areas. |
|
|
|
| 3404.2.3.2 |
8. Large tanks are properly identified with a label and placard. |
|
|
|
| Examine Additional Fire Protection Issues |
Yes |
No |
Comments / Location |
|
|
|
Verify that… |
|
|
|
| 703.2 |
1. Fire doors and smoke barrier doors are not blocked or otherwise made inoperable. |
|
|
|
| 703.2 |
2. Fire door assemblies have not been modified. |
|
|
|
| 703.2.3 |
3. Swinging fire doors close from the full open position and latch automatically. |
|
|
|
| 703.4 |
4. Horizontal and vertical sliding and rolling fire doors have been inspected and tested annually and written proof is available . |
|
|
|
| 703.2.2 |
5. Magnetic hold-open devices are being maintained or are kept closed. |
|
|
|